How to use Equivalent Lengths of Valves and Fittings
One of the most basic calculations performed by any process engineer,
whether in design or in the plant, is line sizing and pipeline pressure
loss. Typically known are the flow rate, temperature and corresponding
viscosity and specific gravity of the fluid that will flow through the
pipe.
These properties are entered into a computer program or
spreadsheet along with some pipe physical data (pipe schedule and
roughness factor)
and out pops a series of line sizes with associated Reynolds
Number, velocity, friction factor and pressure drop per linear
dimension. The pipe size is then selected based on a compromise between
the velocity and the pressure drop. With the line now sized and the
pressure drop per linear dimension determined, the pressure loss from
the inlet to the outlet of the pipe can be calculated.
The
most commonly used equation for determining pressure drop in a straight
pipe is the Darcy Weisbach equation. One common form of the equation
which gives pressure drop in terms of feet of head is given below:
 | Eq. (1) |
The term

is commonly referred to as the Velocity Head.
Another
common form of the Darcy Weisbach equation that is most often used by
engineers because it gives pressure drop in units of pounds per square
inch (psi) is:
 | Eq. (2) |
To obtain pressure drop in units of psi/100 ft, the value of 100 replaces L in Equation 2.
The total pressure drop in the pipe is typically calculated using these five steps.
- Determine the total length of all horizontal and vertical straight pipe runs.
- Determine the number of valves and fittings in the pipe. For example, there may be two gate valves, a 90o elbow and a flow thru tee.
- Determine
the means of incorporating the valves and fittings into the Darcy
equation. To accomplish this, most engineers use a table of equivalent
lengths. This table lists the valve and fitting and an associated length
of straight pipe of the same diameter, which will incur the same
pressure loss as that valve or fitting. For example, if a 2" 90o
elbow were to produce a pressure drop of 1 psi, the equivalent length
would be a length of 2" straight pipe that would also give a pressure
drop of 1 psi. The engineer then multiplies the quantity of each type of
valve and fitting by its respective equivalent length and adds them
together.
- The total equivalent length is usually added to the
total straight pipe length obtained in step one to give a total pipe
equivalent length.
- This total pipe equivalent length is then substituted for L in Equation 2 to obtain the pressure drop in the pipe.
See any problems with this method?
The
following discussion is based on concepts found in reference 1, the
CRANE Technical Paper No. 410. It is the author's opinion that this
manual is the closest thing the industry has to a standard on performing
various piping calculations. If the reader currently does not own this
manual, it is highly recommended that it be obtained.
As in
straight pipe, velocity increases through valves and fittings at the
expense of head loss. This can be expressed by another form of the Darcy
equation similar to Equation 1:
 | Eq. (3) |
When comparing Equations 1 and 3, it becomes apparent that:
 | Eq. (4) |
K
is called the resistance coefficient and is defined as the number of
velocity heads lost due to the valve or fitting. It is a measure of the
following pressure losses in a valve or fitting:
- Pipe friction in the inlet and outlet straight portions of the valve or fitting
- Changes in direction of flow path
- Obstructions in the flow path
- Sudden or gradual changes in the cross-section and shape of the flow path
Pipe
friction in the inlet and outlet straight portions of the valve or
fitting is very small when compared to the other three. Since friction
factor and Reynolds Number are mainly related to pipe friction, K can be
considered to be independent of both friction factor and Reynolds
Number.
Therefore, K is treated as a constant for any given
valve or fitting under all flow conditions, including laminar flow.
Indeed, experiments showed
1 that for a given valve or fitting
type, the tendency is for K to vary only with valve or fitting size.
Note that this is also true for the friction factor in straight clean
commercial steel pipe
as long as flow conditions are in the fully developed turbulent zone. It was also found that the ratio L/D tends towards a constant
for all sizes of a given valve or fitting type
at the same flow conditions. The ratio L/D is defined as the equivalent length of the valve or fitting
in pipe diameters and
L is the equivalent length itself.
In Equation 4,
f
therefore varies only with valve and fitting size and is independent of
Reynolds Number. This only occurs if the fluid flow is in the zone of
complete turbulence (see the Moody Chart in reference 1 or in any textbook on fluid flow). Consequently,
f in Equation 4 is
not the same
f as in the Darcy equation for straight pipe, which
is a function of Reynolds Number. For valves and fittings,
f is the friction factor in the zone of
complete turbulence and is designated
ft, and the equivalent length of the valve or fitting is designated L
eq. Equation 4 should now read (with D being the diameter of the valve or fitting):
 | Eq. (5) |
The equivalent length, L
eq, is related to
ft, not
f,
the friction factor of the flowing fluid in the pipe. Going back to
step four in our five step procedure for calculating the total pressure
drop in the pipe, adding the equivalent length to the straight pipe
length for use in Equation 1 is fundamentally wrong.
So
how should we use equivalent lengths to get the pressure drop
contribution of the valve or fitting? A form of Equation 1 can be used
if we substitute
ft for
f and L
eq for L (with d being the diameter of the valve or fitting):
 | Eq. (6) |
The
pressure drop for the valves and fittings is then added to the pressure
drop for the straight pipe to give the total pipe pressure drop.
Another
approach would be to use the K values of the individual valves and
fittings. The quantity of each type of valve and fitting is multiplied
by its respective K value and added together to obtain a total K. This
total K is then substituted into the following equation:
 | Eq. (7) |
Notice
that use of equivalent length and friction factor in the pressure drop
equation is eliminated, although both are still required to calculate
the values of K
1. As a matter of fact, there is nothing
stopping the engineer from converting the straight pipe length into a K
value and adding this to the K values for the valves and fittings before
using Equation 7. This is accomplished by using Equation 4, where D is
the pipe diameter and
f is the pipeline friction factor.
How
significant is the error caused by mismatching friction factors? The
answer is, it depends. Below is a real world example showing the
difference between the Equivalent Length method (as applied by most
engineers) and the K value method to calculate pressure drop.
The fluid being pumped is 94% Sulfuric Acid through a 3", Schedule 40, Carbon Steel pipe:
Table 1: Process Data for Example Calculation
Mass Flow Rate, lb/hr | 63,143 |
Volumetric Flow Rate, gpm | 70 |
Density, lb/ft3 | 112.47 |
S.G. | 1.802 |
Viscosity, cp | 10 |
Temperature, oF | 127 |
Pipe ID, in | 3.068 |
Velocity, ft/s | 3.04 |
Reynold's No | 12,998 |
Darcy Friction Factor, (f) Pipe | 0.02985 |
Pipe Line ?P/100 ft | 1.308 |
Friction Factor at Full Turbulence (ft) | 0.018 |
Straight Pipe, ft | 31.5 |
Â
Table 2: Fitting Date for Example Calculation
Fittings | Leq/D1 | Leq2, 3 |
K1, 2 =
ft (L/D)
| Quantity | Total Leq | Total K |
90o Long Radius Elbow | 20 | 5.1 | 0.36 | 2 | 10.23 | 0.72 |
Branch Tee | 60 | 15.3 | 1.08 | 1 | 15.34 | 1.08 |
Swing Check Valve | 50 | 12.8 | 0.90 | 1 | 12.78 | 0.90 |
Plug Valve | 18 | 4.6 | 0.324 | 1 | 4.60 | 0.324 |
3" x 1" Reducer4 | None5 | 822.685 | 57.92 | 1 | 822.68 | 57.92 |
Total | Â | Â | Â | Â | 865.63 | 60.94 |
Notes:
- K values and Leq/D are obtained from Reference 1.
- K values and Leq are given in terms of the larger sized pipe.
- Leq is calculated using Equation 5 above.
- The
reducer is really an expansion; the pump discharge nozzle is 1"
(Schedule 80) but the connecting pipe is 3". In piping terms, there are
no expanders, just reducers. It is standard to specify the reducer with
the larger size shown first. The K value for the expansion is calculated
as a gradual enlargement with a 30o angle.
- There
is no L/D associated with an expansion or contraction. The equivalent
length must be back calculated from the K value using Equation 5 above.
Table 3: Pressure Drop Results for Example Calculation
 | Typical Equivalent
Length Method | K Value Method |
Straight Pipe ?P, psi | Not Applicable | 0.412 |
Total Pipe Equivalent Length ?P, psi | 11.734 | Not Applicable |
Valves and Fittings ?P, psi | Not Applicable | 6.828 |
Total Pipe ?P, psi | 11.734 | 7.240 |
The
line pressure drop is greater by about 4.5 psi (about 62%) using the
typical equivalent length method (adding straight pipe length to the
equivalent length of the fittings and valves and using the pipe line
fiction factor in Equation 1).
One can argue that if the fluid is
water or a hydrocarbon, the pipeline friction factor would be closer to
the friction factor at full turbulence and the error would not be so
great, if at all significant; and they would be correct. However
hydraulic calculations, like all calculations, should be done in a
correct and consistent manner. If the engineer gets into the habit of
performing hydraulic calculations using fundamentally incorrect
equations, he takes the risk of falling into the trap when confronted by
a pumping situation as shown above.
Another point to consider is
how the engineer treats a reducer when using the typical equivalent
length method. As we saw above, the equivalent length of the reducer had
to be back-calculated using equation 5. To do this, we had to use
ft and K.
The
1976 edition of the Crane Technical Paper No. 410 first discussed and
used the two-friction factor method for calculating the total pressure
drop in a piping system (
f for straight pipe and
ft for valves and fittings). Since then, Hooper
2 suggested
a 2-K method for calculating the pressure loss contribution for valves
and fittings. His argument was that the equivalent length in pipe
diameters (L/D) and K was indeed a function of Reynolds Number (at flow
rates less than that obtained at fully developed turbulent flow) and the
exact geometries of smaller valves and fittings. K for a given valve or
fitting is a
combination of two Ks, one being the K found in CRANE Technical Paper No. 410, designated K
Y, and the other being defined as the K of the valve or fitting at a Reynolds Number equal to 1, designated K
1. The two are related by the following equation:K = K
1 / N
RE + K
? (1 + 1/D)
The term (1+1/D) takes into account scaling between different sizes within a given valve or fitting group. Values for K
1 can be found in the reference article
2
and pressure drop is then calculated using Equation 7. For flow in the
fully turbulent zone and larger size valves and fittings, K becomes
consistent with that given in CRANE.
Darby
3 expanded on
the 2-K method. He suggests adding a third K term to the mix. Darby
states that the 2-K method does not accurately represent the effect of
scaling the sizes of valves and fittings. The reader is encouraged to
get a copy of this article.
The use of the 2-K method has been
around since 1981 and does not appear to have "caught" on as of yet.
Some newer commercial computer programs allow for the use of the 2-K
method, but most engineers inclined to use the K method instead of the
Equivalent Length method still use the procedures given in CRANE. The
latest 3-K method comes from data reported in the recent CCPS Guidlines
4 and appears to be destined to become the new standard; we shall see.
Consistency,
accuracy and correctness should be what the Process Design Engineer
strives for. We all add our "fat" or safety factors to theoretical
calculations to account for real-world situations. It would be
comforting to know that the "fat" was added to a basis using sound and
fundamentally correct methods for calculations.
D | = | Diameter, ft |
d | = | Diameter, inches |
f | = | Darcy friction factor |
ft | = | Darcy friction factor in the zone of complete turbulence |
g | = | Acceleration of gravity, ft/sec2 |
hL | = | Head loss in feet |
K | = | Resistance coefficient or velocity head loss |
K1 | = | K for the fitting at NRE = 1 |
K? | = | K value from CRANE |
L | = | Straight pipe length, ft |
Leq | = | Equivalent length of valve or fitting, ft |
NRE | = | Reynolds Number |
?P | = | Pressure drop, psi |
n | = | Velocity, ft/sec |
W | = | Flow Rate, lb/hr |
? | = | Density, lb/ft3 |
- Crane Co., "Flow of Fluids through Valves, Fittings and Pipe", Crane Technical Paper No. 410, New York, 1991.
- Hooper, W. B., The Two-K Method Predicts Head Losses in Pipe Fittings, Chem. Eng., p. 97-100, August 24, 1981.
- Darby, R., Correlate Pressure Drops through Fittings, Chem. Eng., p. 101-104, July, 1999.
- AIChE
Center for Chemical Process Safety, "Guidelines for Pressure Relief and
Effluent Handling systems", pp. 265-268, New York, 1998.
Source:
http://www.cheresources.com